tajniak81andClaude Opus 5 cf4fd14b56 The table the charger actually keeps its measurements in
Modbus mode never returned a reading: every status poll came back as "the
charger did not answer", though the charger was answering all along. It was
refusing the question. The A5191 splits its map across two tables where the
spec's single 2xxxx column suggests one — 20000-20100 are input registers and
reject FC03 with an illegal-address exception at every address in the range,
while 21000-21005 really are holding registers and read back over FC03. We
inferred one space from the spec's layout and asked for all of it with FC03.

The client learns FC04, sharing a body with FC03 since the two differ only in
which table the server consults, and the plugin's two measurement reads move to
it. Writes stay on FC06, where the controls already live.

Confirmed against an A5191 on firmware 1.0.6.1: identity, live block and the
control registers all decode as the spec tabulates them.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
2026-09-01 18:42:39 +02:00
..